3 Phase High Frequency Online UPS , high frequency power supply
Key Features:
True double-conversion
DSP technology guarantees high performance
Output power factor 0.8
Wide input voltage range (110-300 VAC)
Active power factor correction in all phases
50Hz/60Hz frequency converter mode
ECO mode operation for energy saving
Accepts dual-mains inputs
Emergency power off function (EPO)
Generator compatible
SNMP+USB+RS-232 multiple communications
3-stage extendable charging design for optimized battery performance
Adjustable battery numbers
Maintenance bypass available
Optional N+X parallel redundancy
Optional isolation transformer offers full isolation and
complete common mode noise rejection
Technical Specifications of Online UPS HP9335C Series:
MODEL |
HP9335C 10-20KVA |
||||||
10K |
10K-XL |
15K |
15K-XL |
20K |
20K-XL |
||
PHASE |
3-phase in / 3-phase out |
||||||
CAPACITY |
10000 VA / 8000 W |
15000 VA / 12000 W |
20000 VA / 16000 W |
||||
INPUT |
|||||||
NominalVoltage |
3 x 400 VAC (3Ph+N) |
||||||
InputVoltageRange |
305-478 VAC (3-phase) at 100% load ; 190-520 VAC (3-phase) at50% load |
||||||
Frequency Range | 46~54 Hz or 56~64Hz | ||||||
Power Factor | 0.99 @ 100% Load | ||||||
OUTPUT |
|||||||
Output Voltage |
3 x 400V (3Ph+N) |
||||||
AC Voltage Regulation (Batt. Mode) |
± 1% |
||||||
Frequency Range(SynchronizedRange) |
46~54Hz or 56~64Hz |
||||||
46~54Hz or 56~64Hz |
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
||||||
Harmonic Distortion |
2 % THD (Linear Load) ; 5 % THD (Non-linear Load) |
||||||
Transfer |
AC Mode to Batt. Mode |
Zero |
|||||
Inverter to Bypass | Zero | ||||||
Waveform (Batt. Mode) | Pure Sinewave | ||||||
EFFICIENCY | |||||||
AC Mode | 89% | 89% | 89% | ||||
Battery Mode | 86% | 88% | 87% | ||||
BATTERY | |||||||
Standard Model |
Battery Type | 12 V / 9 Ah | |||||
Numbers | 20 pcs (18 - 20 adjustable) | 20 pcs x 2 strings (18 - 20 adjustable) | |||||
Typical Recharge Time | 9 hours recover to 90% capacity | ||||||
Charging Current (max.) | 1A | 2A | 2A | ||||
Charging Voltage | 273 VDC ± 1% | ||||||
Long-run Model | Battery Type | Depending on the capacity of external batteries | |||||
Numbers | |||||||
Charging Current (max.) | 4A | 4A | 4A | ||||
Charging Voltage | 273 VDC ± 1% | ||||||
INDICATORS | |||||||
LCD Display | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer,and Fault | ||||||
ALARM | |||||||
Battery Mode | Sounding every 4 seconds | ||||||
Low Battery |
Related Search
High Frequency Power Supply
High Frequency Machine
High Frequency Transformer
High Frequency Welding Machine
High Frequency Heating Machine
High Frequency Welding
More>>
Find more related products in following catalogs on Hisupplier.comCompany InfoChina Electrical Contact Point Online Marketplace [China (Mainland)]
Business Type:Manufacturer You May Like:
Printable Page
Bookmark this page
Sitemap XML About HiSupplier Help Center Customer Service Friend Links Site Map Archives Browse by: China Suppliers - Hot Products - Products Directory - Offers Directory - Suppliers Directory - Buyers Directory Language Option: العربية - Nederlands- Français- Deutsch- Italiano- 日本語- 한국의- Português- Pусский- Español Copyright © HiSupplier.com Online Inc. All Rights Reserved.
|